The Sentinel 150 line provides high performance battery charging for continuous float charge and standby power applications. Switch mode technology provides major advances in power supply and battery charger design, giving a compact and lightweight construction, improved power efficiency, low heat dissipation, wide supply voltage tolerance and low output ripple. The charger is configured for fast, accurate charging to give optimum battery life and reliability. The very smooth output (<1% ripple) allows charging of sealed or vented batteries – e.g., Lead Acid Sealed (VRLA) or use as a stand-alone power supply. Factory calibration is optimized for battery type.
PRODUCT FEATURES:
- AutoBoost
- Alarm Outputs
- Temperature Compensation
- Installation and Connection
PRODUCT SPECIFICATIONS:
- Murphy Part No.: 42703604
- Series: Sentinel UL150
- Operating Voltage: 95 to 250 VAC
- Operating Frequency: 47 - 63 Hz
- Nominal Voltage: 24 VDC
- Battery Type: Vented Lead Acid (12 cells)
- Float Volts: 27.0 VDC
- Boost Volts: 28.2 VDC
- Maximum Current Limit: 5A
- Voltage Ripple: <1%
- Line Regulation: <2%
- Load Regulation: <2%
- Charge Fail, Mains AC Fail: 1 x solid-state relay, + DC during normal charge, open circuit during fault
- Current Rating: 250 mA max @ 30VDC (resistive load), UL class 2
- Operating Temperature: -4 to 140°F (-20 to 60°C)
- Humidity: 20% to 90% RH
- Electrical Safety: 2006/95/EC
- Electromagnetic Compatibility: 2004/108/EC (EN 61000-6-2, EN 61000-6-4)
- UL Approvals: BBGQ: UL1236, CSA22.2 no. 107.2
- Dimensions (w x h1 x h2 x d1 x d2): 4.72 in. x 10.51 in. x 2.76 in. x 3.74 in. x 5.12 in. / 120mm x 267mm x 70mm x 95mm x 130mm
- Weight: 2.8 lb. / 1.25 kg.
Product Condition: NEW